Specifications
and Warranty
|
Part I
General
1.01 Scope
A.
Structural
design. engineering, and fabrication of the entire Skylight System to
include extruded aluminum framing, integral closures, trim, and perimeter
flashing.
B.
Fasteners,
anchors, and related reinforcement of the framing system as required
to resist design loads.
C.
Glass
and glazing materials including gaskets, sealants, setting blocks, backer
rods, and related materials.
D.
Installation
of the entire metal framed skylight system.
1.02 Related Work
A.
Section 05120: Structural Steel
B.
Section 05500: Metal Fabrications
C.
Section
07600: Flashing and Steel Metal
D. Section
08800: Glazing
E. Section
08900: Glazed Curtain Walls
1.03 References
A.
Aluminum
Association (AA): Specifications for Aluminum Structures SAS-30
B.
American
Architectural Manufacturers Association (AAMA)
C.
American
Society for Testing and Materials (ASTM)
D.
American
Institute of Steel Construction (AISC)
E.
American
National Standards Institute (ANSI)
1.04 Performance Criteria
A. Framing
system including glazing material shall be designed to support design
loads as prescribed by the governing building code.
B. Thermal
load of +/- 60 degrees F from ambient temperature without causing bucking,
stresses on glass, failure of seals, undue stress on structural elements,
reduction of performance or other detrimental effects.
C. The
maximum allowable deflection of any framing member normal to the plane
of the glass shall not exceed L/175. For spans 20'-0" or greater the
maximum allowable deflection shell not exceed L/240.
D. The
maximum allowable deflection of any framing member parallel to the plane
of the glass shall exceed/8".
E. Allowable
air infiltration shall not exceed 0.06 CFM of the total glazed surface
area when tested in accordance with ASTM E283 at static pressure of
6.24 PSF.
F. No
uncontrolled water leakage shall occur when the system is tested in
accordance with ASTM E331 at a static pressure of 6.24 PSF.
G. Uniform
load structural according to ASTM E330 +40/-40 PSF, +60/-60 PSF.
1.05 Submittals
A. Product
Data: Submit manufacturer's product data, installation instructions,
use limitations and recommendations for the entire system, including
both published data and specific data prepared for this project.
B. Shop
Drawings: Submit shop drawings for approval prior to fabrication, include
detailed plans, elevations, and details of framing members, glazing
materials, sealants, fasteners, anchors, and thickness and types of
formed flashing and closures. Indicate relationship of adjacent materials.
C. Samples:
Submit the following samples.
1.
Aluminum Finish: Submit color charts or range samples for initial
color selection.
2.
Glazing Materials: Submit verification sample of specified glass,
including any integral color, coatings or frit pattern specified.
1.06 Quality Assurance
A.
Work
of this Section, including design, engineering, fabrication, finishing,
preparation at the job site, erection and glazing of the skylight system
shall be the responsibility of the skylight manufacturer. The manufacturer
shall be regularly engaged in the preceding phases of construction of
skylights and be able to demonstrate that he has successfully performed
on comparable projects over the prior 5 years.
B.
Contract documents are based on products manufactured by FIORE
SKYLIGHTS, Inc. 700 Grace Street, Somerdale, NJ 08083.
1.07 Warranty
A.
Skylight
Manufacturer shall warrant that the framing system will be free of defects
in materials and workmanship for period of five (5) years from date
of completion.
B.
Finish
shall be warranted for a period of one (1) year from date of application.
C.
All
flouropolymer (kynar) finishes shall be warranted for color and film
integrity for a period of five (5) years from date of application.
D.
Glazing
materials shall be warranted against defective materials, delamitation,
seal failure, and defects in manufacturing per the glazing manufacturer's
standard warranties, but not less than five(5) years.
E.
Skylight
Manufacturer/Installer shall guarantee that the installation will remain
weather tight for a period of five (5) years from the date of substantial
completion.
Part II Products
2.01 Framing system
A.
Extruded
aluminum framing members to be 6063-T5, 6063-T6, or 6063T6 alloy and
temper. Other alloys and tempers may be used provided they do not void
the warranties required in paragraph 1.07. Any substituted alloys and
tempers must be clearly indicated on the Shop Drawings and in the structural
calculations.
B. Thickness
of structural framing members shell depend on the design loading, cross
sectional configuration, and fabrication requirements.
C.
Provide
rafters and purlin framing members with tubular profiles and flush condensation
gutters.
D.
All
formed aluminum flashing and closures to be a minimum of 0.060 inches
in thickness.
E.
Snap
on covers and miscellaneous nonstructural trim shall be the minimum
thickness recommended by the Aluminum Extruder.
2.02 Aluminum Finish
All
exposed aluminum shall receive one or more of the following finishes.
(Architect to select)
A. Clear
anodized complying with AAMA 607.1.
B.
Medium Bronze, Dark Bronze, or Black anodized complying with
AAMA 606.1.
C.
Baked
enamel paint complying with AAMA 603.8. Color to be selected by the
Architect.
D.
Two
coat or three coat flouropolymer (Kynar 500) finish complying with AAMA
605.2. Color to be selected by the Architect.
2.03 Glazing
A. Continuous
extruded black E.P.D.M. or silicone compatible gasket.
Harness
(Shore A) 50+/- durometer
Tensile
Strength 2000 psi
Elongation
50%
2.04 Anchors and Fasteners
A. Aluminum
or stainless steel of a type which will not cause electrolytic action
or corrosion.
B. All
exposed fasteners to be finished to match aluminum frame.
2.05 Glazing Material
(See
Specification Section 08800
Type of glazing is determined by the designer based on project requirements.
2.06 Sealants
A.
Skylight
manufacturer shall be responsible for the selection of all sealants.
B. All
surfaces shall be cleaned in accordance with the sealant manufacturers'
guidelines. Skylight Manufacturer shall be responsible for compliance
to sealant manufacturer guidelines.
C. All
exterior seals shall be black in color. (Or standard color sealants
as available)
Part III Installation
A. Strictly
comply with manufacturer's instructions and recommendations. Match profiles,
sizes and spacing indicated on approved shop drawings. Ensure that weep
and condensation control system operates properly. Do not perform structural
silicone sealant work when the air temperature is below 32 degrees F.
B. All
materials shall be delivered, stored, and covered to protect factory
finishes from weather damage and construction dirt until installed.
C. Glazing
materials shall be packaged to prevent breakage.
Part IV Warranty
FIORE
Skylights, Inc. guarantees our structural and standard skylight products
against defects in the workmanship, materials and water leakage for a
certain amount of time depending on the project.
Our
warranty is contingent upon the proper installations in strict accordance
with standard instructions. Our liability under this guarantee shall not
exceed the original purchase price of the defective item, exclusive of
shipping and installation costs.
|
| |
|